Alerton Microset II

Installation and Operations Guide


Introduction

Alerton Microset IIThe Microset™ II is a wall-mounted sensor for BACtalk® VLCs1). Depending on the VLC version, the Microset II may be interchangeable with previous version BACtalk Microsets. See “Compatiblity with Earlier Version VLCs” for details. The Microset II has a backlit liquid crystal display (LCD) and intuitive button operation. It connects to a VLC using three low-voltage wires. The Microset II exchanges data and receives commands from a VLC using a range of AV and BV data points in the VLC that are reserved for Microset operation. These data points are available from the VLC as BACnet objects.

Features

  • Outside temperature displayed at all times
  • Space (room) temperature displayed at all times
  • Optional outside and room himidity display
  • Fan speed display/adjustment (up to three speeds and Off)
  • Setpoint display and adjustment
  • After-hours and housekeeping overrides
  • Heating or cooling mode display
  • English or metric units

Specifications

Table 1: BACtalk Microset II specifications

ThermistorThe thermistor is integrated with the device. The unit is a microprocessor-based sensor with a built-in analog to digital converter for temperature and humidity, which is designed to communicate directly with VLCs
TypeUni-curve Type II
Resistance10kΩ at 77ºF (22ºC)
Interchangeability0.36°F (0.2°)
Time Constant2)10 seconds (to 66% of new temperature)
Stability3)0.036°F (0.02°C) drift per year
Accuracy4) ±0.36°F (0.2°C) over range of 32–158°F (0–70°C)
Power 24 VAC/VDC @ 25mA for backlit display. Orange lead terminates to 24 VAC or 24 VDC terminal on VLC. Sensor draws 5 VDC @ 10 mA from VLC.
VLC connection 24 VAC/VDC @ 25mA for backlit display. Orange lead terminates to 24 VAC or 24 VDC terminal on VLC. Sensor draws 5 VDC @ 10 mA from VLC.
Dimensions 4.6“ (117 mm) H X 3.0” (76 mm) L X 0.7“ (18 mm) D
Humidity sensor Optional
Total accuracy ±2% RH, 0–100% RH @ 25°C, with saturated salt calibration
Operating temp. -40–185°F (-40–85°C)
Repeatability ±0.5% RH
Interchangeability ±5% RH up to 60%RH, ±8% RH at 90% RH (typical humidity)
Ratings Listed Underwriters Laboratory as an accessory for VAVs and VLCs
EMC Directive 89/336/EEC (European CE Mark), pending
FCC Part 15, Subpart J, Class A. pending
1)
The Microset II is not compatible with the Alerton TUX product line
2) , 3) , 4)
Based on normal operating conditions