 ===== Introduction ===== ===== Introduction =====
-{{ :​microsetii.png?​120|Alerton Microset II}}The Microset<​sup>​TM</​sup>​ II is a wall-mounted sensor for BACtalk<​sup>​®</​sup>​ VLCs((The Microset II is not compatible with the Alerton TUX product line)). Depending on the VLC version, the Microset II may be ingterchangeable with previous version BACalk Microsets. See "​Compatiblity with Earlier Version VLCs" on p. 8 for details. The Microset II has a backlit liquid crystal ldisplay (LCD) and intuitive button operation. It connects to a VLC using three low-voltage wires. The Microset II exchanges data and receives commands from a VLC using a range of AV and BV data points in the VLC that are reserved for Microset operation. These data points are available from the VLC as BACnet objects. +Just for playing around.
-==== Features ==== +
-* Outside temperature displayed at all times\\ ​ * Space (room) temperature displayed at all times\\ ​ * Optional outside and room himidity display\\ ​  * Fan speed display/​adjustment (up to three speeds and Off)\\ ​  * Setpoint display and adjustment\\ ​  * After-hours and housekeeping overrides\\ ​  * Heating or cooling mode display\\ ​  * English or metric units\\  +
-===== Specifications ===== +
-Table 1: BACtalk Microset II specifications\\  +
-|**Thermistor**|The thermistor is integrated with the device. The unit is a microprocessor-based sensor with a built-in analog to digital converter for temperature and humidity, which is designed to communicate directly to VLCs| +
-|Type |Uni-curve Type II| +
-|Resistance|10kΩ at 77ºF (22ºC)| +
-|Interchangeability|0.36°F (0.2°)| +
-|Time Constant((Based on normal operating conditions))|10 seconds (to 66% of new temperature)| +
-|Stability((Based on normal operating conditions))|0.036°F (0.02°C) drift per year| +
-|Accuracy((Based on normal operating conditions)) |±0.36°F (0.2°C) over range of 32–158°F (0–70°C)| +
-|**Power** |24 VAC/VDC @ 25mA for backlit display. Orange lead terminates to 24 VAC or 24 VDC terminal on VLC. Sensor draws 5 VDC @ 10 mA from VLC. | +
-|**(VLC connection** |24 VAC/VDC @ 25mA for backlit display. Orange lead terminates to 24 VAC or 24 VDC terminal on VLC. Sensor draws 5 VDC @ 10 mA from VLC. | +
-|**Dimensions** |4.6" (117 mm) H X 3.0" (76 mm) L X 0.7" (18 mm) D | +
-|**Humidity sensor** |Optional | +
-|   Total accuracy | ±2% RH, 0–100% RH @ 25°C, with saturated salt calibration| +
-|   ​Operating temp. |-40–185°F (-40–85°C) | +
-|   ​Repeatability |±0.5% RH | +
-|   ​Interchangeability |±5% RH up to 60%RH, ±8% RH at 90% RH (typical humidity)| +
-| **Ratings** |Listed Underwriters Laboratory as an accessory ​for VAVs and VLCs\\ EMC Directive 89/336/EEC (European CE Mark), pending\\ FCC Part 15, Subpart J, Class Apending | +