| ID | Display or control function | Description | Remarks |
| | Setpoint (°F or °C as appropriate)
Override time remaining
ON/OFF status
Time of day (optional alternate)
Value associated with data code (field service mode) | Displays unit setpoint, after-hours/housekeeping timer, ON/OFF status, or value of field service code, depending on mode of operation. Optionally, in modes M1-M6, the time of day can display alternately on a three-second cycle with any of the above. | * Setpoint = AV90
* Housekeeping timer or after-hours timer = AV98
* ON/OFF mode = BV65
* Time of day is read directly from the VLC when BV82 is ON. The VLC must be time-synced. BV83 controls format (12-or 24-hour). |
| Outside air temperature (OAT)
Outside humidity (optional alternate) | Displays OAT. Optionally, an outside humidity reading in %RH can display alternately on a three-second cycle with the OAT. | OAT = AV103, which is written to in DDC.
%RH = AV107. If AV107 is non-zero display will cycle. |
| Fan status | Displays occupant-selected fan status and speed in modes M4, M5, M8, and M9. In these modes, the occupant can use the right UP/DOWN buttons to increase and decrease the fan speed. In other modes, occupant adjustment is disallowed, but DDC can control the fan status and speed display, nonetheless. | Only one of the following BVs may be ON; otherwise, the Microset II indicates a high fan speed:
* Blank = BVs 72-74 OFF
* Low = BV72 ON
* Med = BV73 ON
* High = BV74 ON |
| Space temperature
Space humidity (optional alternate for MS-2000H)
Field service code (field service mode) | Displays space (room) temperature. The Microset II with humidity sensor (MS-2000H), can display the room %RH alternately with the room temperature on a three-second cycle. | Space temperature = AV101. AI-0 is room temperature as read by the Microset II thermistor. VLC DDC must transfer AI-0 to AV101 for space temperature display.
Display will cycle between space temperature and humidity if BV84 is ON.
Space humidity = AV102. No DDC required. AV102 cannot store other values. |
| Right UP / DOWN buttons
* Fan speed control (M4, M5, M8)
* After-hours increment/decrement (M2, M5)
* ON/OFF control (M3, M6)
* Housekeeping timer ON/OFF (M7, M9)
* Adjust value (field service mode) | Button press causes only affected value on LCD to appear; all others disappear. Display remains in this state for three seconds after button release. | Button press affects BV67 according to mode (see Table 4 on p. 13). In fan modes, button press also affects BVs 72–74 (Table 7 on p. 26). |
| Left UP / DOWN buttons
* Adjust setpoint
* Display unoccupied heating / cooling setpoints (M2, M5)
* Scroll through codes (field service mode) | Button press causes only affected value on LCD to appear; all others disappear. Display remains in this state for three seconds after button release. | |