===== VLC DDC BV and AV assignments ===== Each VLC has a number of pre-assigned data points -- binary and analog values (BVs and AVs) -- which are used to control the Microset II and read status from it. These data points are available from the VLC as BACnet objects. BACnet-compliant devices can access the properties of these objects. For a complete reference of objects and properties available in VLCs, see the //Programmer's Guide and Reference for BACtalk Systems // (LTBT-TM-PRGRMR). |< 90% 90px - >| | Note |The following tables reflect only with the Present Value property of the AV and BV objects. These are listed as data points.| ==== BV assignments ==== |< 100% 70px 60px - - - >| ^ Point ^ Read only ^ Description ^ On action or status ^ Off action or status ^ | BV64 | NA |Controls occupied/unoccupied or rented/vacant status (see [[devices:microset:ddc-operating-modes|DDC operating modes]])|Sets Microset II to occupied or rented operation|Sets Microset II to unoccupied or vacant operation| | BV65 | NA |Sets On/Off mode (see [[devices:microset:ddc-operating-modes|DDC operating modes]])|Enables On/Off mode|Disables On/Off mode| | BV66 | ✔ |Override status. Activated in unoccupied or vacant modes when the user initiates override from the Microset II|On when override timer (AV98) is non-zero|Off when the override timer (AV98) is zero| | BV67 | ✔ |Occupied status. Reflect the value of BV64 or BV66. Also reflects user selection of On/Off mode when BC64 is On (see [[devices:microset:ddc-operating-modes|DDC operating modes]])|Space is occupied. Current setpoint values (AV99, AV100) are calculated using occupied logic|Space is unoccupied. Current setpoint values (AV99, AV100) are calculated using unoccupied logic| | BV68 | NA |Field service mode and balance mode lockout|Lock out both field service and balance modes|Allow either field service or balance mode| | BV69 | NA |English/metric mode swap (see[[devices:microset:mode-swap-measure|DDC operating modes]]|Swap native units mode between English and metric|Uses units as determined by VLC native units| | BV70 | ✔ |Microset connection status|Microset detected|Microset not detected| | BV71 | ✔ |Native unit mode status from the native mode set in the VLC DDC header|English units|Metric units| | BV72((DDC can write to these BVs. They are also affected by the occupant selection of fan speed. Only one of these BVs can be ON at once; otherwise, the fan displays high fan status. When fan is OFF, these BVs are OFF.)) ((Not available in VLC versions 1.06c and earlier. See “Compatibility with Earlier Version VLCs”))| NA |Fan low speed|Enable fan low speed status indicator at Microset II| | | BV73((DDC can write to these BVs. They are also affected by the occupant selection of fan speed. Only one of these BVs can be ON at once; otherwise, the fan displays high fan status. When fan is OFF, these BVs are OFF.)) ((Not available in VLC versions 1.06c and earlier. See “Compatibility with Earlier Version VLCs”))| NA |Fan medium speed|Enable fan medium speed status indicator at Microset II| | | BV74((DDC can write to these BVs. They are also affected by the occupant selection of fan speed. Only one of these BVs can be ON at once; otherwise, the fan displays high fan status. When fan is OFF, these BVs are OFF.)) ((Not available in VLC versions 1.06c and earlier. See “Compatibility with Earlier Version VLCs”))| NA |Fan high speed|Enable fan high speed status indicator at Microset II| | | BV,,, | NA |And there are more descriptions|more On statuses|and more Off statuses| ==== AV assignments ==== |< 100% 60px 60px - - - >| ^ Point ^ Read only ^ Description ^ On action or status ^ Off action or status ^ | AV90 | NA |Controls occupied/unoccupied or rented/vacant status (see [[devices:microset:ddc-operating-modes|DDC operating modes]])|Sets Microset II to occupied or rented operation|Sets Microset II to unoccupied or vacant operation| | AV91 | NA |Sets On/Off mode (see [[devices:microset:ddc-operating-modes|DDC operating modes]])|Enables On/Off mode|Disables On/Off mode| | AV92 | NA |Controls occupied/unoccupied or rented/vacant status|Sets Microset II to occupied or rented operation|Sets Microset II to unoccupied or vacant operation| | AV93 | NA |Controls occupied/unoccupied or rented/vacant status|Sets Microset II to occupied or rented operation|Sets Microset II to unoccupied or vacant operation| | AV94 | NA |Controls occupied/unoccupied or rented/vacant status|Sets Microset II to occupied or rented operation|Sets Microset II to unoccupied or vacant operation| | AV95 | NA |Controls occupied/unoccupied or rented/vacant status |Sets Microset II to occupied or rented operation|Sets Microset II to unoccupied or vacant operation| | AV96 | NA |Controls occupied/unoccupied or rented/vacant status |Sets Microset II to occupied or rented operation|Sets Microset II to unoccupied or vacant operation|